Datalogger
WSD10TCOPM - Indoor temperature - CO₂ concentration - PM2.5 particulate - PM10 particulate
4-channel Wireless Smart Data Logger - Indoor temperature, CO2 concentration, PM2.5 particulate matter and PM10 particulate matter - Dual internal lithium ‘D’ batteries for up to 4 years of battery life with sampling every 90 minutes.
€ 1.076,90
VAT and shipping excluded
Contact us
- Technical data
- Downloads
- Related products
- Case Studies
| Power supply | · Double 19Ah - 3,6V type “D” lithium internal battery · Possibility of external power supply via USB-C input (5Vdc 1A) |
| Battery life (*)(with radio signal quality at least sufficient) | · Up to 4 years – Sampling interval: 85 minutes · Up to 3 years – Sampling interval: 60 minutes · Up to 1.5 years – Sampling interval: 30 minutes · Up to 9 months – Sampling interval: 15 minutes |
| Measures acquired ( 4 input channels) |
· Indoor temperature · CO₂ concentration · PM2.5 particulate· PM10 particulate |
| Sampling interval (*) | Selectable from one minute to 24 hours (90 minutes default) |
| Datalogger capacity | 64,000 samples (for each channel) |
| Working temperature | · Operative: -10°C ÷ +60°C · Warehousing: -40°C ÷ +70°C |
| Radio frequency | ISM 868MHz |
| Radio coverage | Up to 6Km in line of sight(can be extended using WR12 battery powered repeaters) |
| Sealing | IP30 |
| Dimensions | 155x120x50mm |
| Weight | 500g |
| Case material | ABS |
| Mounting | Fix on 3 points |
| Connections | Wireless, USB |
| Indoor temperature - Transducer type | NTC10KΩ |
| Indoor temperature - Measure range | -10°C ÷ +60°C |
| Indoor temperature - Measure accuracy | ±0.2°C in whole range |
| Indoor temperature - Measure resolution | 0.01°C |
| CO2 - Measure fundamental | NDIR principle |
| CO2 - Measure range | 5,000ppm |
| CO2 - Measure accuracy | < ±50ppm +3% of measure acquired |
| CO2 - Measure resolution | 1ppm |
| CO2 - Compensations | Compensation of temperature and atmospheric pressure |
| CO2 - Calibrations | No calibration needed. Periods of fresh air presence are NOT required for auto-zeroing. |
| PM2.5 and PM10 particulate - Measure fundamental | Laser-based scattering |
| PM2.5 and PM10 particulate - Measure range | 1 to 1,000μg/m3 |
| PM2.5 and PM10 particulate - Measure accuracy | · ±10μg/m3@0 to 100μg/m3 · ±10%@100 to 1,000μg/m3 |
| PM2.5 and PM10 particulate - Measure resolution | 1μg/m3 |
| PM2.5 and PM10 particulate - Certifications | MCERTS |
* battery life may be influenced by fieldwork conditions, sampling interval and system configuration.
** radio coverage reachable using up to 32 WR12 repeaters (maximum 16 for each path) between the device and the gateway.