EN
EN IT FR

Products

Datalogger

WLRD12-4DI - LoRa pulse counter

WineCap™ LoRa Datalogger with 4 channels - Interface module equipped with 4 inputs for counting pulses with clean contact or "open-collector" type acquired from the output of meters - Independently configurable channels for the acquisition of active, reactive and apparent energy, thermal energy, gas, fluid volume and generic pulses - Generic pulses with scalable cumulative counting function - Internal “C” type lithium battery for an autonomy of up to 7 years with sampling every 10 minutes - IP65.

€ 338,80 VAT and shipping excluded
Contact us
  • Technical data
  • Downloads
  • Related products
Power supply 8.5Ah - 3.6V type “C” lithium internal battery (BAT2)
Battery life (*) Up to 7 years (samples every 60 minutes and radio signal quality at least sufficient)
Measures acquired ( 4 input channels) Pulses from clean contact or open collector configurable as: · Active electric energy [KWh]· Reactive electric energy [Kvarh]· Apparent electric energy [Kvah]· Thermal energy [KWh]· Fluid volume [l]· Generic pulses· Generic pulses with scalable aggregate count Compatible with any digital energy meter with pulse output.
Sampling interval (*) Selectable from one minute to 24 hours ( 60 minutes default)
Datalogger capacity 64,000 samples (for each channel)
Working temperature · Operative: -30°C ÷ +60°C· Warehousing: -40°C ÷ +70°C
Radio frequency ISM 868MHz
Radio coverage Up to 15Km in line of sight(can be extended using WLRE battery powered enhancers)
Sealing IP65
Dimensions 90x120x50mm
Weight 350g
Case material ABS
Mounting Fix on 4 points
Connections Wireless, USB
Cable external diameter 4.7mm maximum
Copper wire section 0.05 ÷ 2.5mm² / ÷ 14 AWG
Optional accessories · Energy meters· Rogowski coils· Open/closed TA (current transformers) · POD counter pulse acquisition interface (EXP2PUL)
Pulse input - Connection Internal clamping screw terminal block
Pulse input - Transducer input From 0 to 4.5mm Ø gland
Pulse input - Count maximum frequency 40Hz with pulse time set to 10msec
Pulse input - Count weight Selectable using management software

* battery life may be influenced by fieldwork conditions, sampling/measuring interval and system configuration.