Datalogger
WLRD40COPM - CO₂ concentration - Atmospheric pressure - PM2.5 particulate - PM10 particulate
WineCap™ LoRa® 4-channel Data Logger - CO2 concentration, atmospheric pressure, PM2.5 particulate matter and PM10 particulate matter.
€ 1.076,90
TVA et frais de port exclus
Nous contacter
- Données techniques
- Téléchargements
- Produits connexes
| Power supply | 2 internal lithium “D” batteries, 19 Ah - 3.6 V (BAT3)Optional external power supply via USB Type-C input (5 Vdc 1 A) |
| Battery life (*) | Up to 4 years (acquisition every 60 minutes and at least sufficient radio signal) |
| Measured quantities (4 channels) | · CO₂ – Carbon dioxide concentration [ppm] · Atmospheric pressure [mbar] · PM2.5 – Fine particulate matter [μg/m³] · PM10 – Inhalable particulate matter [μg/m³] |
| Sampling interval (*) | Selectable from 1 minute to 24 hours (default: 60 minutes) |
| Datalogger capacity | 65 000 measurements (per channel) |
| Operating temperature | · Operation: -10°C to +60°C· Storage: -40°C to +70°C |
| Radio frequency | ISM 868 MHz |
| Line-of-sight radio coverage (**) | Up to 15 km (extendable using WLRE battery-powered enhancers) |
| Protection rating | IP30 |
| Dimensions (W x H x D) | 155 × 120 × 50 mm |
| Weight | 500 g |
| Enclosure material | ABS |
| Mounting | 3-point mounting |
| Connections | Wireless, Mini USB 2.0 |
| CO₂ concentration – Measurement principle | Dual-wavelength NDIR sensor with integrated auto-calibration |
| CO₂ concentration – Measurement range | 0–5 000 ppm |
| CO₂ concentration – Measurement resolution | 1 ppm |
| CO₂ concentration – Measurement accuracy | 0–5 000 ppm: < ±(50 ppm + 3% of reading) |
| CO₂ concentration – Compensations | Compensated for temperature and atmospheric pressure |
| CO₂ concentration – Calibrations | No calibration required. No need for ambient air zeroing periods |
| Atmospheric pressure – Measurement range | 700–1 100 mbar |
| Atmospheric pressure – Measurement resolution | 0.1 mbar |
| Atmospheric pressure – Accuracy at 25°C | Typical: ±2 mbar (20–80% RH) |
| Atmospheric pressure – Temperature dependence | ±0.015 mbar/K |
| Particulate matter PM2.5 and PM10 – Measurement principle | Laser-based scattering |
| Particulate matter PM2.5 and PM10 – Measurement range | 0–1 000 μg/m³ |
| PM2.5 – Measurement accuracy range 0–100 μg/m³ | ±5 [μg/m³ + 5 % of reading] |
| PM2.5 – Measurement accuracy range 100–1000 μg/m³ | ±10 % of reading |
| PM10 – Measurement accuracy range 0–100 μg/m³ | ±25 μg/m³ |
| PM10 – Measurement accuracy range 100–1000 μg/m³ | ±25 % of reading |
| Particulate matter PM2.5 and PM10 – Measurement resolution | 0.1 μg/m³ |
| Particulate matter PM2.5 and PM10 – Certifications | MCERTS |
* battery life may be influenced by fieldwork conditions, sampling/measuring interval and system configuration.** radio coverage can be extended using up to 32 enhancer WLRE (maximum 16 for each path) between the device and the gateway.